86
Using ProLink
®
Software with Micro Motion
®
Transmitters
Configure Menu: Characterize
continued
Pressure compensation with RFT9739
8.7 Pressure compensation
with RFT9739
A Version 2 or Version 3 RFT9739 can compensate for the effect of
pressure on sensor flow tubes. Pressure effect is defined as the change
in sensor flow sensitivity due to process pressure change away from
calibration pressure. Sensors that are affected by pressure are listed in
Table 8-4
, page 87.
In applications where the operating pressure varies significantly from the
pressure at which the flowmeter was calibrated, the user can establish
pressure compensation. Pressure effect can be corrected in one of two
ways:
• For real-time compensation, by entering pressure correction factors
and connecting an external pressure transmitter
• For relatively stable operating pressures, by adjusting the calibration
factors for flow and density
Real-time compensation
For real-time pressure compensation, two pressure compensation
factors must be entered, one for flow and one for density. In the FlowFact
and/or DensFact text boxes, enter the appropriate values from
Table 8-4
, then click OK.
• The pressure correction factor for flow is the percent change in the
flow rate per psi.
• The pressure correction factor for density is the grams per cubic
centimeter change in density per psi.
The user should also enter the calibration pressure for real-time
pressure compensation. In the FlowCal Pressure text box, enter the
appropriate value in psi, then click OK. (At the factory, Micro Motion
sensors are calibrated for flow at 20 psig.)
In addition, real-time pressure compensation requires either gauge
pressure or analog pressure input. (To select an input for pressure
compensation, see
Section 11.3
, page 122.)
Gauge pressure input
If a pressure transmitter connected to a host controller measures gauge
pressure at the sensor input, the RFT9739 can use flow and density
signals from the sensor, and pressure signals from the host controller, to
compensate for the pressure effect on the sensor.
• In a HART-compatible network, the RFT9739 functions as a primary
or secondary master while polling the host controller.
• In a Modbus-compatible network, the host controller downloads
pressure values to register 40007 or register pair 20257-20258.
Analog pressure input
The RFT9739 can be connected to an analog pressure transmitter that
produces a 4-20 mA input signal representing pressure. The RFT9739
or an external source can power the pressure transmitter.
• To connect a pressure transmitter to the RFT9739, see the RFT9739
instruction manual.
• If a sensor is ordered for an application requiring pressure
compensation, the pressure input is configured at the factory.
Komentarze do niniejszej Instrukcji